UPS Runtime and Load Calculator
Estimate UPS load, rated watt capacity and idealized battery runtime from VA, power factor, battery voltage and amp-hours. Real runtime depends on the battery and discharge curve; check the maker's chart.
Result
| Rated watt capacity | 1,350 W |
|---|---|
| Load | 37.0% |
| Nominal battery energy | 432 Wh |
| Idealized runtime | 44.1 minutes |
Note: This is an energy estimate, not a manufacturer runtime curve. Battery age, temperature, inverter self-consumption, high discharge rate, battery chemistry, and cutoff voltage can materially reduce runtime. Use the UPS maker's runtime chart for purchasing decisions.
Learn more
How it works
A UPS has two limits. The watt rating (VA x power factor) is the most load it can carry at all. The battery energy (voltage x amp-hours, in watt-hours) decides how long it can carry that load.
Runtime here is usable battery energy divided by the load: watt-hours x efficiency / load watts x 60 gives minutes. Efficiency covers the loss converting battery DC to AC; 85-90% is typical for small units.
This is an idealized figure. Batteries deliver less energy at high discharge rates, when cold, and as they age, so a real UPS at high load often runs well short of this number. Use it to compare options and sanity-check, then confirm with the maker's runtime chart.
Worked example
A 1500 VA UPS with a 0.9 power factor and a 24 V, 18 Ah battery bank, carrying a 500 W load:
| Watt capacity | 1500 x 0.9 = 1,350 W |
|---|---|
| Load | 500 / 1,350 = 37.0% |
| Battery energy | 24 x 18 = 432 Wh |
| Usable at 85% | 432 x 0.85 = 367.2 Wh |
| Idealized runtime | 367.2 / 500 x 60 = 44.1 minutes |
What is the difference between VA and watts?
VA is apparent power; watts are the real power your equipment uses. The power factor links them. Check your load in watts against VA x power factor.
Where do I find the battery voltage and Ah?
On the battery label or the UPS spec sheet. A 24 V bank is often two 12 V batteries in series; the Ah stays the same as one battery.
How much headroom should I leave?
Many admins keep steady load under about 80% of the watt rating so startup surges and added equipment do not trip the UPS.
Does doubling the load halve the runtime?
Not quite. The formula assumes it does, but lead-acid batteries deliver more of their energy at lower discharge rates, so real runtime beats the formula at light load and falls short at heavy load.